The product is mainly suitable for distribution lines with rated voltage up to and including 0.6/1kV.
- nominal voltage: 0.6/1kV
- Long-term working temperature:
Insulate material |
temperature |
PVC |
70℃ |
- Short-circuit carrying temperature:
Insulate material |
temperature |
PVC |
160℃ |
- Cable laying temperature: above 0℃.
- Operating ambient temperature: -15℃/70℃
- The bending radius of the cable:
- The bending radius of the cable which is single-core and unarmoured shall not be less than 20OD, but armored shall not be less than 15D.
- The bending radius of the cable which is multi-core and unarmoured shall not be less than 15OD, but armored shall not be less than 12D.
- (OD: The outside diameter of the cable.)
- Flame-retardant performance complies with standard GB/T 18380.3.